For self-starters
who know what they want!
Vane relay JSL-1E, mechanical Standard 1
  • Vane relay JSL-1E, mechanical Standard 1
  • Vane relay JSL-1E, mechanical Standard 2
  • Vane relay JSL-1E, mechanical Standard 3

Vane relay JSL-1E, mechanical

Description
Technical data:
• Switching capacity: 15 (8) A, 24–250 V ~, for 24 V ~ min. 150mA
• Switching differential: > = 1 m / s
• Contact: 1 micro-switch used as floating changeover contact (changeover switch)
• Protection type: IP 65 (after installation, on media side: IP 20)
• Protection class: I
• Ambient temperature: –40 to +80 °C
• Max. medium temperature: 85 °C
• Min. switch-on value: 2m/s
• Min. switch-off value: 1m/s
• Max. switch-on value: 9.2 m/s
• Max. switch-off value: 8.0/s
• Lever: Brass
• Vane: V2A (1.4301)
• Colour: grey (lower: RAL 7016, upper: RAL 7035)
Application:
• Monitoring of air flows in ducts, in supply-air and waste-air devices of fans or electric heating registers.
• The air-direction relay is set to the minimum switching point before delivery
• The switch-on/switch-off value can be increased by rotating the internal screw clockwise
• Installed vertically from above in a horizontal pipe/channel
Order No.€/eachAvail.Functions
60 044 07not logged in
© 2017 TBS Technischer Bedarf GmbH. All rights reserved.
Tel. +49 74 33.98 92 57 · Fax +49 74 33.98 92 58